2 Results for the search " lightning performance of distribution lines":
On the Mitigation Effect of Surge Arresters on the Lightning Performance of Overhead Distribution Lines
Description:
For the accurate statistical assessment of the lightning performance of distribution lines one needs to
take into account the presence of protection devices such as surge arresters and shielding ... see morewire/neutral
groundings. Indeed, the presence of those devices can significantly modify the indirect lightning
response of the overhead line and, therefore, the relevant lightning performance.
In particular, this paper aims at investigating the impact of the presence of surge arresters on the
indirect lightning performance of overhead distribution lines having realistic configuration.
Specifically, reference is made to typical Italian distribution lines. The investigation is performed with
the help of a statistical procedure developed by the authors – based on the Monte Carlo method and of
the use of an accurate modelling/calculation tool for the induced surges – that has been recently
compared with one proposed in the IEEE 1410 Std for the same purpose, and shown to be more
complete and suitable for the problem of interest. The paper also aims at investigating the influence of
the presence of surge arresters on the indirect lightning surges transferred through power transformers.
Such an additional investigation is performed by means of a suitable high-frequency power
transformer mode integrated with the lightning-induced computation tool.
Authors: A. Borghetti, F. Napolitano, C.A. Nucci and M. Paolone - University of Bologna, Italy
CIGRE – Colloquium Cavtat - Application of Line Surge Arresters in Power Distribution and Transmission Systems
Tag(s): Lightning statistics, induced overvoltages, lightning performance of distribution lines, surge arresters, shielding wires groundings, Monte Carlo method.
Correlation of lightning events and faults in distribution power networks
Description:
The paper deals with the analysis of the possible correlation between cloud-to-ground lightning discharges and relay operations inferred by using the experimental data obtained means of a measurement ... see moreset-up, installed on an Italian MV distribution network, and a statistical procedure based on the coordinated use of the Italian Lightning Location System (LLS) CESI-SIRF, the monitoring systems of protection manoeuvres and an advanced simulation tool for the calculation of lightning induced overvoltages. The procedure takes into account the uncertainties related to the estimation of lightning stroke location and current amplitude provided by the LLS. The experimental set-up, composed by a distributed monitoring system, is able to measure a-periodic voltage transients characterized by a frequency content up to 4 MHz. Three of these units have been installed in the feeder of a three-phase overhead distribution network with a total length of 21 km. The same feeder is protected with overcurrent and zero-sequence relays whose operations are recorded by a monitoring system with a 10-ms sampling time. The data collected during one year of operation of the experimental set-up have been analyzed together with the data collected by the LLS for a 144 km2 area covering the equipped feeder and its surrounding area, in order to account for all direct and indirect lightning events that may have caused a relay intervention. The data have been also used to test the calculation model. The paper eventually reports the results of the correlation analysis carried out using the mentioned procedure, which is used to evaluate the probability that a specific event, detected by the LLS and time-correlated to relay operation, may have been the cause of a flashover in the network.
Authors: A. Borghetti, F. Napolitano, C.A. Nucci, M. Paolone, M. Bernardi, F. Rachidi, K. Yamabuki
CIGRE 2008 - a joint research project
Tag(s): Lightning protection, lightning-to-fault correlation, lightning location systems, lightning performance of distribution lines, induced overvoltages, a-periodic voltage transient measurement, EMTP.