27 Results for the search "AdminEMTP-RV":
Ferro_hyst_Zno
Description:
Simple ferroresonance case. In this case the switching of a part of the network comprised of a cable connected to a no-load transformer is carried out. A pole of the breaker fails to open and an impor... see moretant and stable ferroresonance phenomena appears.
The ferroresonance problem, whether in a general circuit or in a power-system circuit, is usually tackled in one of two ways : circuit configuration (i.e series and/or parallel) or nonlinearities (i.e saturation and hysteresis of transformers). A fundamental factor to the occurence of ferroresonance is the nonlinear magnetizing characteristic of the transformer and the capacitive coupling.
In this case a 250 kVA, 20/0.4 kV transformer is used. This transformer is represented by the hysteresis transformer model. The hysteresis element has been used as the magnetization branch of the one-phase transformer model. A 200 m cable is used for the study. This cable is modelled by a PI-section. The short circuit power of the source is about 150 MVA.
In order to reduce overvoltages caused by ferroresonance, surge arresters are installed. Two questions have emerged : will the arresters mitigate ferroresonance, and will they fail during ferroresonance ? Simulations in different transient regimes can be carried out in order to determine the maximal current, overvoltages (voltage at the end of the cable for instance), energy absorbed by the arresters
Tag(s): Protection
Comp_bctran_3Wind
Description:
A good case of comparison between BCTRAN and the regular encapsulated model available in the transformers library during transient state.
Tag(s): Transformers
Cross_Bonded_Cable
Description:
Insulation coordination - 225 kV cross bonded cable - protection of the sheath.
In the configuration a 225 kV cross-bonded cable is connected at both ends to an otherhead line. The sheath is prot... see moreected by star-connected arresters.
The modelling used is adapted for the study of Fast-Front-Overvoltages (see IEC 60071)
A current source, with a CIGRE concave shape (See CIGRE 63 document), representing a lightning stroke has been connected to a tower close to the cable.
The case includes the modelling of the different elements of the configuration (cable, spans, arresters...).
CB_arc_CM
Description:
This is an interesting case of the study of arc-circuit interaction in case of the interruption of a short-line fault.The arc is represented by a composite Cassie-Mayr model and the line is represente... see mored as frequency-dependant.
The case shows the application of black-box arc modeling in the study of kilometric-line fault capability of a 420 kV circuit-breaker. By zooming on the arc current and voltage near current-zero, post-arc current and initial TRV may be visualized in both cases of clearing and thermal failure.
Tag(s): Example, Protection
3-phase_Statcom_Prel_Version
Description:
This is a three-phase three level Statcom model with PWM controller for use in transmission and distribution systems. It works quite well under severe perturbation.
The official version of this s... see moretatcom will be available in version 1.1 to be release in mid-june 2004.