122 Results for the search " ":
Induction machine modeling for distribution system analysis using initialization and time-domain methods
Description:
Panel session paper to be presented at the IEEE T&D show in New Orleans (Oct. 2005)
Authors: J. Mahseredjian, S. Dennetière, B. Khodabakhchian and A. Xémard
Abstract:
This pap... see moreer is presented as part of an effort by the Distribution System Analysis Subcommittee to establish reference cases for induction machine modeling in distribution system analysis and unbalanced three-phase systems. This panel paper presents analysis results obtained when applying a full time-domain method with load-flow and steady-state initialization. The selected software is EMTP-RV. Problem solution complexities are discussed.
Interpolation and reinitialization for the simulation of power electronic circuits
Description:
Authors:
Ming Zou, Jean Mahseredjian, Geza Joos, Benoît Delourme, Luc Gérin-Lajoie
Abstract:
This paper presents a new interpolationreinitialization method for transient simulat... see moreions in both forced commutation and natural commutation conditions occurring in power electronic circuits. Recently methods in this field are also discussed.
Line_Coupling
Description:
The following example demonstrates the coupling effect between 3 adjacent transmission lines.
The case study consists of the implementation of a third transmission line next to two existing... see more lines. The data of the geometrical configuration are entered in the DATA LINE module and are stored in the "line_couplin_CP.lin". The generated model was obtained using the CP option and are loaded to the CP m-phase module using the data included in the "line_coupling_CP_rv.csv" file. The results are very close to the measurements provided in "H.W. DOMMEL ET AL, CASE STUDIES FOR ELECTROMAGNETIC TRANSIENTS, P.1,1991".
Look what happens without EMTP-RV
Description:
This is a nice video about the switching of a shunt reactor (most probably 500 kV) with a Circuit-Switcher.
>A circuit-switcher is a SF6 load-break swith with no fault current breaking cap... see moreability. The load current, in this case around 150 A, is normally interrupted first by the 2 interrupters and then the disconnect will open to isolate the reactor.
What happened in this video:
1 - During the opening, an external flashover occurs on one of the chamber most probably because of the contamination;
2 - The other chamber can not withstand the whole voltage and reignites internally;
3 - The external flashover vanishes because an arc is established inside;
4 - The disconnect opens on the full load current;
5 - The arc burns freely in the air for some 10 seconds until it is self-extinguished or eliminated by a circuit-breaker operation.
Motor_Protection
Description:
The following circuit presents a protection scheme for an induction motor due to voltage dips.
The voltage dip generator is presented in a masked subcircuit where it is possible to control ... see morethe shape and duration of the voltage dip.
Tag(s): Motor, Protection