29 Results for the search "Example":
CB_arc_CM
Description:
This is an interesting case of the study of arc-circuit interaction in case of the interruption of a short-line fault.The arc is represented by a composite Cassie-Mayr model and the line is represente... see mored as frequency-dependant.
The case shows the application of black-box arc modeling in the study of kilometric-line fault capability of a 420 kV circuit-breaker. By zooming on the arc current and voltage near current-zero, post-arc current and initial TRV may be visualized in both cases of clearing and thermal failure.
Tag(s): Example, Protection
Line_Coupling
Description:
The following example demonstrates the coupling effect between 3 adjacent transmission lines.
The case study consists of the implementation of a third transmission line next to two existing... see more lines. The data of the geometrical configuration are entered in the DATA LINE module and are stored in the "line_couplin_CP.lin". The generated model was obtained using the CP option and are loaded to the CP m-phase module using the data included in the "line_coupling_CP_rv.csv" file. The results are very close to the measurements provided in "H.W. DOMMEL ET AL, CASE STUDIES FOR ELECTROMAGNETIC TRANSIENTS, P.1,1991".
Non_Linear_Benchmark
Description:
Benchmark case for testing the nonlinear solution method of transients simulation packages.
This case shows the superior capability of EMTP-RV to handle simultaneous solutions of three very... see more nonlinear elements: Circuit-breaker arc , Hysteretic characteristic of transformers and Zinc-Oxide arresters.
Tag(s): Example
PM_subcircuit
Description:
Example of a user defined model. In this case a line-start permanent magnet synchronous machine is connected to a simple power network. This machine, working as a generator, has been modeled by contro... see morel elements. This user defined model is not recomme.
The line-start permanent magnet motor is a high-efficiency synchronous motor with self starting capability when operating from a fixed frequency voltage source. The permanent magnets embedded in its rotor provide the synchronous excitation and the rotor cage provides the induction motor torque for starting. The difference in permeability between the magnet and rotor core also results in significant magnetic saliency and reluctance torque at synchronous speed. At asynchronous speeds, the dc excitation and saliency of the permanent magnets will cause pulsating torque components. When the field strength of the magnet is too strong, a line-start permanent magnet motor may fail to synchronize because of the excessive pulsating torque component from the dc-excitation of the magnet.
The objective of this case is to create a user defined model of a permanent magnet synchronous machine. With this model the user can explore the behaviour of the torque components during a starting run of the generator from standstill. In particular, we will examine the ability of the motor to synchronize with various values of magnet field strength, mechanical loading and rotor inertia.
This case also shows the capabilities of EMTP-RV to create user defined models. This model assembled with control elements is particularly clear. I needed 4 hours to create this model and to validate it with an existing Simulink model ! The user can see the whole model with its equations on one page (see Figure below)
This model is given as an example of user defined model and should not be used for other purposes.